Energy Meters


Two SO-outputs for pulse or limit values

Dimensions: 96 X 96 X 46 mm

Programmable conversion factors

Flexible power supply with an AC/DC wide-range power supply unit

Electrically isolated current inputs (1 A or 5 A)

Accurate measured values for U, I <= 0.5%, F <= 0.02 Hz, others 1%

Storage of minimum and maximum values

Measurement in single-phase systems, 3-wire and 4-wire systems in 4 quadrant operation


Two SO-outputs for pulse or limit values

Dimensions: 144 X 144 X 46 mm

Programmable conversion factors

Flexible power supply with an AC/DC wide-range power supply unit

Electrically isolated current inputs (1 A or 5 A)

Accurate measured values for U, I <= 0.5%, F <= 0.02 Hz, others 1%

Storage of minimum and maximum values

Measurement in single-phase systems, 3-wire and 4-wire systems in 4 quadrant operation


4-quadrant measurement of all values in AC systems

Dimensions: A230: 144 X 144 X 46 mm / A230s: 96 X 96 X 46 mm

Safe 3-way galvanic isolation between all circuits

2 outputs for pulse or limit values

4 meter for active power: Incoming/outgoing with high/low tariff

Accurate measured values for U, I <= 0.2%, P, Q, S, PF, meter: 0.5% F: 0.02 Hx

All counter values, recorded values and settings are kept on a power supply failure

Application: Single-phase 3L, balanced/unbalanced (Aron, Full), 4-L balanced/unbalanced


Multifunctional Power Meter for 3-Phase Systems

Data logger now with 250,000 entries

RS232 and RS485 interfaces included

Versions available for PROFIBUS, Modbus, LON and Ethernet

Adjustable voltage and current transformer ratios

Single device for 1 A and 5 A current transformers

Limit value and analog outputs included as standard equipment

Connection with Kieback&Peter DDC3000 via SBM51/13


Active Energy, 2-Wire AC Systems, PTB Approval, 5 (65) A, LCD

Active Energy measurement (import) per EN 61036, class 1 with electronic anti-reversing

Instantaneous power for the evaluation of momentary circuit loads

Direct 5 (65) A connection without additional current transformers

Export variant available for 60 Hz line frequency

Displays installation errors without additional measuring equipment

SO pulse output or 230 B, adjustable pulse rate and pulse duration

Mounts to DIN rail per EN 50022


Active Energy, 4-Wire 3-Phase Current, PTB Approval, 5 (65) A, LCD

Active Energy measurement (import) per EN 61036, class 1 with electronic anti-reversing

Instantaneous power for the evaluation of momentary circuit loads

Direct 5 (65) A connection without additional current transformers

Export variant available for 60 Hz line frequency

Displays installation errors without additional measuring equipment

SO pulse output or 230 B, adjustable pulse rate and pulse duration

Mounts to DIN rail per EN 50022


Active Energy, 2-Wire AC Systems, PTB Approval, 1//5 A, LCD

Active Energy measurement (import) per EN 61036, class 1 with electronic anti-reversing

Instantaneous power for the evaluation of momentary circuit loads

Transformer connection 5//1, adjustable, calibratable transformation ratios

Export variant available for 60 Hz line frequency

Displays installation errors without additional measuring equipment

SO pulse output or 230 B, adjustable pulse rate and pulse duration

Mounts to DIN rail per EN 50022


Active Energy, 3-Wire 3-Phase Current, PTB Approval, 1//5 A, LCD

Active Energy measurement (import) per EN 61036, class 1 with electronic anti-reversing

Instantaneous power for the evaluation of momentary circuit loads

Transformer connection 5//1, adjustable, calibratable transformation ratios

Export variant available for 60 Hz line frequency

Displays installation errors without additional measuring equipment

SO pulse output or 230 B, adjustable pulse rate and pulse duration

Mounts to DIN rail per EN 50022


Active Energy, 4-Wire 3-Phase Current, PTB Approval, 1//5 A, LCD

Active Energy measurement (import) per EN 61036, class 1 with electronic anti-reversing

Instantaneous power for the evaluation of momentary circuit loads

Transformer connection 5//1, adjustable, calibratable transformation ratios

Export variant available for 60 Hz line frequency

Displays installation errors without additional measuring equipment

SO pulse output or 230 B, adjustable pulse rate and pulse duration

Mounts to DIN rail per EN 50022


Active Energy, 4-Wire 3-Phase Current

Acquires active energy

Electrical connection with reversed polarity is indicated by means of an LED

Direct connection or via transformer

7-digit drum-type counter mechanism

Direct connection 5 (65)A U389A / Transformer connection 5//1 U389B

Pulse Output (SO) for energy import

Mounts to DIN rail per EN 50022


Summator, 24 Metering Channels

Processes pulse signals and is capable of recognizing digital states

Allows for logging, visualization and optimization of all electrical and non-electrical energies

Up to 24 pulse signals can be connected

32 processing channels

Data exchange with the PC via RS232 interface

Additional RS232 interface allows for radio controlled clock for system time or a report printer

Multi-master compatible ECS LAN for connection to other units over a network


Summator, 12 Universal Inputs, LON-Bus

Expands the ECS to include processing of analog values - connection via LON bus

Allows for logging, visualization and optimization of all electrical and non-electrical energies

Up to 12 analog or pulse signals can be connected

64 processing channels

Data exchange with the PC via RS232 interface

Additional RS232 interface allows for radio controlled clock for system time or a report printer

Multi-master compatible ECS LAN for connection to other units over a network


LON Micro-Summator

Used as a PC adapter or a LON interface for the ECS-LAN

Not equipped with its own display or control elements

Up to 63 U168X electrical energy meters can be connected via electrically isolated LON

          interface 

64 processing channels over defined periods of time at a programmable interval

Data exchange with the PC via two RS232 interfaces

Multi-master compatible ECS LAN for connection to other units over a network


Mini-Summator, 6 Inputs, LON

Used as a PC adapter or a LON interface for the ECS-LAN

Not equipped with its own display or control elements

Up to 63 U168X electrical energy meters can be connected via electrically isolated LON

          interface 

64 processing channels over defined periods of time at a programmable interval

Data exchange with the PC via two RS232 interfaces

Multi-master compatible ECS LAN for connection to other units over a network

Daytronic

U.S.A. manufacturer of signal conditioning instruments and systems for industrial, automotive and aerospace applications. As a sister company to Camille-Bauer, Daytronic manages and supports all Camille-Bauer products, including the SINEAX and KINAX, in the US market.

view all info

Gossen- Metrawatt

German manufacturer of Power Instrumentation and Temperature Controllers, Power Analyzers, Hand-held instruments, Laboratory & Rack Mount Power Supplies. Daytronic supports and manages the SYSKON and KONSTANTER Series power supplies.

view all info

Dranetz

U.S.A. based manufacturer of Power Quality Analyzers for fixed mount and portable applications. Supports and manages the GMC-I - Gossen Metrawatt products in the US market.

view all info

Electrotek Concepts

Electrotek Concepts, a leading power systems engineering consultant. We analyze, measure, simulate and solve electric power problems and provide training on many power quality and power system topics.

view all info